2.2 Wiring

When conduct wiring, follow the instructions below.

Use shield wire for control signal line and ground the unit with shield wire.

Applicable wire size for TB1 is 0.2 to 2.5mm

2

.

For TB2, it is 0.2 to 1.5mm

2

.

Peel off the end of the wire by about 5mm (7mm for TB1).

For connecting wires, use screwdriver that has a blade tip of 0.4mm thickness and 2.5mm width.

(For TB3, thickness and width should be 0.6mm and 3.5mm.)

Tightening torque of the terminal block should be 0.22 to 0.25N

m .

(For TB1, it is 0.5 to 0.6N

m.)

Never bind the signal line and main circuit connection wire together.

Separate the signal line and the main circuit connection wire by more than 200mm.

Use 0.75mm

2

wire for the connection of PGCC terminal of the option side and CC terminal of the inverter.

Use 0.75mm

2

wire for the connection of grounding terminal of the option side and that of the inverter.

„

< PG interface > [ TB2 terminal]

Terminal

name

Function

Specification

Internal circuit

PGA1

PGA2

PG feedback input,
Pulse row speed
command input
(Phase A input)

PGB1

PGB2

PG feedback input
Pulse row speed
command input
(Phase B input)

PGZ1

PGZ2

PG feedback input
Pulse row speed
command input
(Phase Z input)

PG feedback

15V complementary / open
collector

12V complementary / open
collector

Maximum input frequency

60kpps (2 phases)
120kpps (single phase)

Pulse duty

50 ± 10%

Photocoupler

:1.2~1.7V

PGVC

PGCC

PG power supply terminal 12VDC

160mA or less