beautypg.com

Caution, D. installing adaptor and termination cap, Masonry factory built wood burning – Quadra-Fire QVI-30FB-S User Manual

Page 14

background image

Quadra-Fire • QVI-30FB-S • 2020-910 Rev. H • 6/09

14

D. Installing Adaptor and Termination Cap

For installation of termination cap see minimum vent
heights for various pitched roofs (see Figure 7.3).

To install adaptor see Figure 7.4.

Roof Pitch H (Min.) Ft.
Flat to 6/12....................1.0*
Over 6/12 to 7/12 ........1.25*
Over 7/12 to 8/12 ..........1.5*
Over 8/12 to 9/12 ..........2.0*
Over 9/12 to 10/12 ........2.5*
Over 10/12 to 11/12 ..... 3.25

Figure 7.3 Minimum Height from Roof to Lowest Discharge
Opening

* 3 foot minimum in snow regions

Roof Pitch H (Min.) Ft.
Over 11/12 to 12/12 ....... 4.0
Over 12/12 to 14/12 ....... 5.0
Over 14/12 to 16/12 ....... 6.0
Over 16/12 to 18/12 ....... 7.0
Over 18/12 to 20/12 ....... 7.5
Over 20/12 to 21/12 ....... 8.0

CLASS A PIPE

Figure 7.4

Damper Flashing Kit (Optional)

For use with LINK-DV4-30B Liner Kit.

Note: Damper may have to be removed to use this kit.

• Run fl ex liners through 3” holes in damper fl ashing.

• Attach damper fl ashing to fi rebox roof with self tapping

screws included in kit.

Figure 7.5

To help eliminate cold air drafts, it may be necessary to
place non-combustible insulation around the fl ues as they
go though the damper.

Note: The LINK-DV4-30B system REQUIRES this
insulation.

Masonry

Factory Built

Wood Burning

EXHAUST

AIR

VENT PIPE

TERMINATION

CAP

LINK-DV30B

Installation

LINK-DV4-30B

Installation

INLET AIR

VENT PIPE

WARNING:

DO NOT BLOCK

THIS PIPE END!

INLET AIR

VENT PIPE

EXHAUST

AIR

VENT PIPE

Note: Untwist
the pipe while
extending it, to
achieve full 30’
length.

Remove 18 inch x 18 inch fl ashing on cap by removing
3 screws. Connect both the LINK-ZC-ADPB to Class
A Pipe and the termination cap to the LINK-ZC-ADPB
with the self tapping screws provided.

OPTIONAL LINK-ZC-ADPB

FOR USE WITH CLASS A

WOODBURNING PIPE

Í

OR

Î

CAUTION

Sharp Edges
• Wear protective gloves and safety

glasses during installation.

HORIZONTAL

OVERHANG

VERTICAL

WALL

GAS DIRECT VENT
TERMINATION CAP

12

X

ROOF PITCH

IS X/ 12

LOWEST

DISCHARGE

OPENING

2 FT.

MIN.

20 INCHES MIN.

H (MIN.) - MINIMUM HEIGHT FROM ROOF
TO LOWEST DISCHARGE OPENING