beautypg.com

Model number structure, Ordering information, Specifications – Omron DeviceNet Communications Unit E5ZN-DRT User Manual

Page 3: E5zn-drt, Model number legend, List of models, Ratings

background image

E5ZN-DRT

Model Number Structure

Model Number Legend

Ordering Information

List of Models

Note: A DeviceNet Communications Unit and Terminal Unit are required to connect to DeviceNet. Two End Plates are provided with E5ZN-SCT24S

Terminal Units. When mounting to a DIN track, be sure to mount End Plates on both sides.

Specifications

Ratings

Note: 1. Do not use an inverter output as the power supply. (Refer to Safety Precautions for All Temperature Controllers.)

2. The power consumption for the Temperature Controllers is not included.

1

E5ZN-DRT

1.

DRT: DeviceNet communications

Name

External input power

supply voltage

Applicable Temperature

Controller

Model

DeviceNet Communications Unit 24 VDC

E5ZN

E5ZN-DRT

Terminal Unit

E5ZN-SCT24S

Power supply voltage

DeviceNet

24 VDC (for internal circuits)

External input power supply

24 VDC (for RS-485 communications circuits and Temperature Controllers)

Allowable voltage range

DeviceNet

11 to 25 VDC

External input power supply

20.4 to 26.4 VDC

Power consumption
(See note 2.)

DeviceNet

Approx. 1.1 W (for a current of 45 mA at 24 VDC)

External input power supply

Approx. 0.5 W (for a current of 20 mA at 24 VDC)

Connectable Temperature Controllers

E5ZN Series

Maximum number of connectable Temperature Controllers 16

Ambient operating temperature

−10 to 55°C (with no icing or condensation)

Ambient operating humidity

25% to 85%

Ambient storage temperature

−25 to 65°C (with no icing or condensation)

http://www.ia.omron.com/

3