beautypg.com

Omega CN3440 User Manual

Page 11

background image

9

4

ELECTRICAL INSTALLATION…

Fig. 4.5 Cable Glands

4.4.3

Cable Glands

(N. American – 0.5in) – Fig. 4.5

Warning.

Controller glands must be fitted with a
face seal.

Torque settings (hubs only) – 20ft. lbs
minimum, 25ft. lbs. maximum.

Outer nuts – hand tight plus a half turn
only.

Information.

Suitable Cable Glands: (mandatory for
FM installations):

O.Z. GEDNEY
SR-50-375 or SR-504
APPLETON
CG 3150 or CG-3150S (and STG-
50 sealing ring).
THOMAS & BETTS
2521.

When fitting cable glands to the
controller, start with an outer gland
and also temporarily fit a gland at the
opposite end, to aid location of the
transmitter gland plate. Fit and tighten
glands consecutively from initial
gland.

Fittings
vary
slightly
for
different
makes

Outer Nut

Alternative
Face Seal

Face
Seal

Hub

Illustration
typical for
O.Z.Gedney