beautypg.com

Omega CN3440 User Manual

Page 10

background image

8

…4

ELECTRICAL INSTALLATION

4.4

Cable Glands

and Conduit Fixings

4.4.1

Cable Glands

(IEC – 20mm) – Fig. 4.3

4.4.2

Conduit Adaptors

(N. American – 0.5in) – Fig. 4.4

Warning.

Rigid conduit must NOT be fitted to the
controller.

Controller adaptors must incorporate
a face seal.

Torque settings for the hubs and outer
nuts on the specified adaptors is 20ft.
lbs minimum, 25ft. lbs. maximum.

Information.

Suitable adaptors for controller
(mandatory for FM installations):

APPLETON
ST-50 PLUS STG-50 or STB-50
PLUS STG-50.
Reusable ONLY with replacement
ferrule STF-50.
O.Z. GEDNEY
4Q-50, 4Q50T or 4Q-50TG.

Fig. 4.4 Conduit Adaptors

'O'-Ring

Fig. 4.3 Cable Gland

(Supplied as standard)

Ferrule

Outer Nut

Seal
(Present
in O.Z.
Gedney
Fittings)

Alternative
Face Seal

Face
Seal

Hub