Gas inserts, Clearances, Combustible mantels – Regency U31-LP2 User Manual

Page 2

background image

Clearances

Unless otherwise stated the clearances listed below are Minimum
distances to combustible materials. Please Note: A major cause
of chimney related fi res is due to a failure to maintain required
clearances (air space) to combustible materials. It is of the greatest
importance that this fi replace and vent system be installed only in
accordance with these instructions.

Combustible Mantels

Because of the extreme heat this fi replace emits, the mantel
clearances are critical.
Combustible mantel clearances from top of
the louvers are shown in the diagram below. Mantel may be installed
anywhere in the shaded area or higher.

Note: A non-combustible mantel may be installed at a lower

height.

Note: Ensure the paint that is used on the mantel and the facing

is “heat resistant” or the paint may discolour.

G

H

I

A

D

B

E

F

C

Clearances to Combustibles

Dimension

Description

U31

A

From Unit to Sides

10” (254mm)

B

From Unit to Ceiling

47-1/2” (1207mm)

C

From Unit to Mantel

see mantel clearances

D

From Standard Surround to Sides

4” (102mm)

E

From Standard Surround to Ceiling

41-1/2” (1054mm)

F

Minimum Mantel Height

13” (330mm)

G

Maximum Mantel Depth

12” (305mm)

H

Minimum Alcove Width

48” (1219mm)

I

Maximum Alcove Depth

36” (914mm)

*No Hearth Required

Clearances when installed with a Zero Clearance Kit

Dimension

Description

U31

F

Minimum Mantel Height

20” (508mm)

G

Maximum Mantel Depth

11-1/2” (292mm)

NOTE: Mantel clearances for Installation into a Zero Clearance Kit

are different. Please refer to the Zero Clearance Kit Manual
for details.

U31 Regency Gas Insert

120

August 2008 Product Specifi cations Book

Gas Inser

ts

Gas Inserts