background image

Catalog No.: 2000.202P

Effective: 12-1-07

Replaces: 10-15-03

Raytherm - Type H

Hydronic Heating Boilers

Model


MODELS H 514-824

Indoor and Outdoor

Dimensions (Inches)

Approx.

Model MBTU MBTU Width

Flue

Dia.

Shipping

No. Input Output A K L

Weight

(Lbs.)

H-514 511.5 419.4 32-3/4 10 25-3/8 475

H-624 627.0 514.0 37-1/2 12 29-1/2 485

H-724 726.0 595.0 41-5/8 12 34-1/4 635

H-824 825.0 676.5 45-3/4 14 38-1/2 645

NOTE: Ratings shown are for elevations up to 2,000 feet. For elevations over 2,000 feet, reduce ratings

at the rate of 4% for each 1,000 feet above sea level.

BOILER RATE OF FLOW AND PRESSURE DROP

Model

10°

∆T 20°

∆T

30°

∆T

40°

∆T

No. GPM

∆P FT

GPM

∆P FT

GPM

∆P FT

GPM

∆P FT

H-514 84 7.8 42 1.9 N/A N/A N/A N/A

H-624 N/A N/A 51 3.0 N/A N/A N/A N/A

H-724 N/A N/A 60 4.4 40 2.0 N/A N/A

H-824 N/A N/A 68 6.0 45 2.6 N/A N/A

N/A – Not Applicable

NOTES:
ƒ Values represent maximum flows and pressure drops for closed heating systems.
ƒ Maximum acceptable flow through heat exchanger tubes is 90 GPM.