Roberts Gorden Vantage TF TF-160 User Manual
Page 13
SECTION 4: N
ATIONAL
S
TANDARDS
AND
A
PPLICABLE
C
ODES
7
SECTION 4: NATIONAL STANDARDS AND
APPLICABLE CODES
4.1 Gas Codes
The type of gas appearing on the nameplate
must be the type of gas used. Installation must
comply with national and local codes and
requirements of the local gas company.
United States: Refer to National Fuel Gas Code,
ANSI Z223.1 - latest revision (same as NFPA
54).
Canada: Refer to CAN/CGA B149.1 and B149.2:
Installation Codes for Gas Burning Appliances.
4.2 Aircraft Hangars
Installation in aircraft hangars must be in
accordance with the following codes:
United States: Refer to Standard for Aircraft
Hangars, ANSI/NFPA 409 - latest revision.
Canada: Refer to Standard CAN/CGA B149.1
and B149.2.
• In aircraft storage and servicing areas, heaters
shall be installed at least 10' (3 m) above the
upper surface of wings or of engine enclosures
of the highest aircraft which may be housed in
the hangar. The measurement shall be made
from the wing or engine enclosure (whichever is
higher from the floor), to the bottom of the heater.
• In shops, offices and other sections of aircraft
hangars communicating with aircraft storage or
servicing areas, heaters shall be installed not
less than 8' (2.4 m) above the floor.
• Suspended or elevated heaters shall be so
located in all spaces of aircraft hangars that they
shall not be subject to injury by aircraft, cranes,
movable scaffolding or other objects. Provisions
shall be made to assure accessibility to
suspended heaters for recurrent maintenance
purposes.
4.3 Public Garages
Installation in garages must be in accordance
with the following codes:
United States: Standard for Parking Structures
NFPA 88A - latest revision or the Code for Motor
Fuel Dispensing Facilities and Repair Garages,
NFPA 30A - latest revision. Canada: Refer to
CAN/CGA B149.1 and B149.2: Installation
Codes for Gas Burning Appliances.
• Heaters must not be installed less than 8'
(2.4 m) above the floor. Minimum clearances to
combustibles must be maintained from vehicles
parked below the heater.
• When installed over hoists, minimum
clearances to combustibles must be maintained
from the upper most point of objects on the
hoist.
4.4 Electrical
The heater must be electrically grounded in
accordance with the following codes:
United States: Refer to National Electrical
Code
®
, ANSI/NFPA 70 - latest revision. Wiring
must conform to the most current National
Electrical Code
®
, local ordinances and any
special diagrams furnished.
Canada: Refer to Canadian Electrical Code,
CSA C22.1 Part 1 - latest revision.
4.5 Venting
The venting must be installed in accordance
with the requirements within this manual and
the following codes:
United States: Refer to NFPA 54/ANSI Z223.1 -
latest revision, National Fuel Gas Code.
Canada: Refer to CAN/CGA B149.1 and
B149.2: Installation Codes for Gas Burning
Appliances
4.6 High Altitude
These heaters are approved for installations up
to 2000' (US), 4500' (Canada) without
modification. Consult factory if US installation is
above 2000' (610 m) or Canadian installation is
above 4500' (1370 m).