Roberts Gorden Vantage TF TF-160 User Manual
Page 11
SECTION 3: C
RITICAL
C
ONSIDERATIONS
5
NOTE: 1. All dimensions are from the surfaces of all tubes, couplings and elbows.
2. Clearances B, C and D can be reduced by 50% after 25' (7.5 m) of tubing downstream
from where the burner and burner tube connect.
FIGURE 5: U-TUBE, STANDARD REFLECTOR
(inches)
(centimeters)
Model
A
B
C
D
A
B
C
D
TF-120
6
35
63
30
16
89
161
77
TF-160
6
38
69
37
16
97
176
94
TF-200
6
40
76
39
16
102
194
100
TF-250
6
46
79
43
16
117
201
110
TF-300
6
50
84
47
16
127
214
120
TF-350
8
54
87
51
21
138
221
130
TF-380
8
54
87
51
21
138
221
130
A
C
D
B
FIGURE 6: U-TUBE, 45
°
(inches)
(centimeters)
Model
A
B
C
D
A
B
C
D
TF-120
8
8
60
42
21
21
153
107
TF-160
8
8
66
46
21
21
168
117
TF-200
8
8
74
52
21
21
188
133
TF-250
8
8
78
61
21
21
199
155
TF-300
8
8
84
66
21
21
214
168
TF-350
8
8
85
70
21
21
216
178
TF-380
8
8
85
70
21
21
216
178
B
C
D
A
FIGURE 7: U-TUBE, OPPOSITE 45
°
REFLECTOR
(inches)
(centimeters)
Model
A
B
C
D
A
B
C
D
TF-120
8
54
60
22
21
138
153
56
TF-160
8
60
66
22
21
153
168
56
TF-200
10
64
74
22
26
163
188
56
TF-250
10
70
78
22
26
178
199
56
TF-300
12
74
84
22
31
188
214
56
TF-350
12
76
85
22
31
194
216
56
TF-380
12
76
85
22
31
194
216
56
A
C
D
B