· Table C-3: R7184 Troubleshooting

continued from previous page

Procedure Status

Corrective

Action

Burner starts.

Trouble is in thermostat circuit. Check thermostat
wiring connections.

If connections are clean and tight, check
thermostat wires for continuity.

· Disconnect line voltage power and open line

switch.

· Check all wiring connections.
· Tighten any loose connections and recheck.
· If burner still doesn't start, replace R7184

5. Jumper thermostat (T -T)

terminals on R7184

IMPORTANT

First remove one thermostat
lead wire.

Burner does not start.

If burner still doesn't start, check the oil burner
motor. It may be seized or burned out.

Condition: Burner starts then locks out on safety with indicator light flashing at 1 Hz rate (½ second
on, ½ second off)

Procedure Status

Corrective

Action

1. Check that the limit

switches are closed and
contacts are clean.

- - -

- - -

2. Check for line voltage

power at the oil primary
control. Voltage should be
120 vac (nominal)

- - -

- - -

Indicator light is on.

Cad cell or controller is defective, sees external
light, or connections are shorted. Go to step 4.

3. Check indicator light with

burner off, no call for heat
(no flame).

Indicator light is off.

Go to step 5.

Indicator light turns off.

Eliminate external light source or permanently
shield cad cell.

4. Shield cad cell from

external light.

Indicator light stays on.

· Replace cad cell with new cad cell and

recheck.

· If indicator light does not turn off, remove cad

cell leadwires from R7184 and recheck.

· If indicator light turns off, replace cad cell

bracket assembly.

· If indicator light does not turn off, replace

controller.

Continued on next page