Table a-3 direct drive blower set-up, Table a-4 direct drive blower characteristics – Royal Appliance Air Furnace User Manual
Page 19
29733 R2 06/01/2003
19
TABLE A-3 DIRECT DRIVE BLOWER SET-UP
BLOWER SET-UP
COOLING CAPACITY
0.20 in. w.c.
0.50 in w.c.
FURNACE
MODEL
BLOWER
MOTOR
HP
Speed Speed
Htg. CFM
Range
1
Tons
2
MOTOR
HP
Clg. CFM
Range
80F (060)
Low
Med - Low
629 - 972
80F (070)
Med - Low
Med - High
792 - 1223
80F (080)
G10 DD
½
Med - High
High
857 - 1324
3
½
900 - 1150
120F (090)
Med - Low
Med - High
976 - 1508
120F (100)
Med - High
High
1084 - 1676
120F (120)
G10 DD
½
High
High
1279 - 1977
3
½
800 - 1300
120F (090)
Low
Low
1106 - 1843
120F (100)
Med - Low
Med - Low
1229 - 2048
120F (120)
G12-10 DD
¾
Med - High
High
1450 - 2417
5
¾
1400 - 1870
(1)
Heating Range values based on temperature rise. Upper values may exceed measured airflow values in Table A-3.
(2)
Nominal Values Only
TABLE A-4 DIRECT DRIVE BLOWER CHARACTERISTICS
CFM
External Static Pressure - inches w.c.
Furnace
Model
Motor
hp
Blower
Temp.
Rise
(
DT)
Motor
FLA
Speed
0.20 0.30 0.40 0.50 0.60 0.70
High 1368 1298 1223 1144 1046 938
Med-High 1318 1256 1178 1108 1007 909
Med-Low 1173 1132 1071 993 909 816
80F
½
G10 DD
60° - 90°F
7.7
Low 856 833 791 748 692 610
High 1604 1527 1446 1360 1245 1092
Med-High 1507 1425 1338 1270 1171 1035
Med-Low 1172 1146 1119 1064 977 879
120F
½
G10 DD
55° - 85°F
7.7
Low 810 771 731 690 645 597
High 1957 1911 1846 1797 1729 1658
Med-High 1764 1730 1695 1640 1584 1526
Med-Low 1677 1658 1603 1565 1506 1424
120F
¾
GT12-10 DD
45° - 75°F
12.5
Low 1446 1446 1446 1404 1315 1245