Installation, Masonry and factory built fireplace clearances, Optional flue connector kit – Regency I2100M User Manual
Page 7
Regency Insert & Hearth Heater
7
Clearance diagram for installations
INSTALLATION
Side and Top facing is a maximum of 1.5" thick.
Floor protection must non-combustible, insula-
tive material with an R value of 1.1 or greater.
*
If the hearth extension is flush with the floor
(F) it must extend 19.5" in front of the body
face (E).
Note: Hearth Extension Width (G) is
measured from edge of fuel door
to side of hearth.
**
A non-combustible mantel may be
installed at a lower height if the fram-
ing is made of metal studs covered
with a non-combustible board.
MASONRY AND FACTORY BUILT FIREPLACE CLEARANCES
The minimum required clearances to combustible materials when installed into a masonry or factory built fireplace are listed below.
Adjacent
Mantle**
Top
Side
Minimum
Minimum
Minimum
Unit
Side Wall
(to Top)
Facing
Facing
Hearth
Hearth
Hearth Side
(to Side)
(to Top)
(to Side)
Extension*
Thickness*
Extension
A
B
C
D
E
F
G
Small Flush
Insert (I1100S) 15"/380mm
20"/510mm
14"/355mm
7.375"/187mm 16"/406mm
1.5"/38mm
8"/205mm
Medium Flush
Insert (I2100M) 10"/255mm
17"/430mm
10.25"/260mm
8"/203mm
16"/406mm
1.5"/38mm
8"/205mm
Large Flush
Insert (I3100L) 13"/330mm
19"/480mm
18"/455mm
6.5"/165mm
16"/406mm
1.5"/38mm
8"/205mm
Hearth Heater
(H2100M)
10"/255mm
25"/635 mm
14"/355mm
8.5"/216mm
18"/455mm
1.5"/38mm
6"/152mm
View from Rear of Insert
OPTIONAL FLUE
CONNECTOR KIT
The optional Flue Connector Kit (Part # 846-527)
and the Straight Flue Adaptor (Part #846-504)
shown here, may be used to produce a secure
connection between your flue connector and
the insert collar. Detailed installation instructions
are included with the kit.
Position the grill on the inside bodyface side and
fasten using the bolts, washers and nuts pro-
vided (2 per side) as shown in the diagrams.
Note: The grill has a front and rear, the
holes on the front side have
rounded edges and the rear holes
have flat edges.