GAS PIPE PRESSURE

TESTING

The appliance must be isolated from the gas
supply piping system by closing its individual
manual shut-off valve during any pressure
testing of the gas supply piping system at test
pressures equal to or less than 1/2 psig. (3.45
kPa). Disconnect piping from valve at pressures
over 1/2 psig.

CONVERSION TO LOWER BTU RATING

THIS CONVERSION MUST BE DONE BY A QUALIFIED GAS

FITTER IF IN DOUBT DO NOT DO THIS CONVERSION !!

Natural Gas Conversion Kit 730-920
Contains:
Qty. Part # Description
1 904-240 Burner Orifi ce #37 (Natural Gas)
1 918-034 Decal "Converted to 30,000 Btu"
1 918-033 Instruction Sheet

Propane Conversion Kit 730-922
Contains:
Qty. Part # Description
1 904-390 Burner Orifi ce #52 (Propane)
1 918-034 Decal "Converted to 30,000 Btu"
1 918-033 Instruction Sheet

Additional Piece (pkg. with unit):
1

Log Bracket Restrictor

1) Shut off the gas supply.

2) Open the front door. Carefully remove the

logs and lava rock.

3) Remove burner. See diagram below.

Burner Orifi ce

4) Unscrew the 2 Rear

Log Pins and move
to the front hole
position.


5) Remove Rear Log

Bracket and slide
the Log Bracket
Restrictor between
the Rear Log Bracket

Position the Log Bracket Restrictor between

the Rear Log Bracket and the burner.

6) Remove burner orifi ce with a 1/2" wrench

and discard.

The manifold pressure is controlled by a regulator
built into the gas control, and should be checked
at the pressure test point.

Note: To properly check gas pressure, both

inlet and manifold pressures should
be checked using the valve pressure
ports on the valve.

1) Make sure the valve is in the "OFF"

position.

2) Loosen the "IN" and/or "OUT" pressure

tap(s), turning counterclockwise with a 1/8"
wide fl at screwdriver.

3) Attach manometer to "IN" and/or "OUT"

pressure tap(s) using a 5/16" ID hose.

4) Light the pilot and turn the valve to "ON"

position. Read manometer.

5) The pressure check should be carried out

with the unit burning and the setting should
be within the limits specifi ed on the safety
label.

6) When fi nished reading manometer, turn

off the gas valve, disconnect the hose and
tighten the screw (clockwise) with a 1/8" fl at
screwdriver. Note: Screw should be snug,
but do not over tighten

7) Reinstall new burner orifi ce (NG stamped

#37 or LP stamped #52) and tighten.

8) Reverse steps 3) and 2).

9) Adjust Vent restrictor setting: To set the

Vent restriction as indicated in the diagram,
simply loosen the screws and push the vent
restrictor plate to the correct position. Tighten
the screws.

Unit Btu/h

Restrictor

Opening

U39 38,000

A

1-3/4"

(44mm)

30,000

B

1-1/4"

(32mm)

Note: Use a

magnetic type

screwdriver if

possible.

and the burner, secure with the 2 screws.

Vent Restrictor set-

ting at High Btu/h

Vent Restrictor set-

ting at Low Btu/h

10) Attach the label "This unit has been

converted to..." on top of the Serial # decal
over the higher Btu information.

11) Check for gas leaks.

12) Check inlet and outlet pressures.

13) Check operation of fl ame control. Check

for proper fl ame appearance and glow on
logs.