Hi delta – type p, Cold water run option – Raypak HI DELTA 1802B User Manual
Page 3

Hi Delta – Type P
Models 1532B-2342B
(Cold Water Run Option)
Model
*Separate 120 VAC or 240 VAC 1Ø power required for Cold Water Run option
** Requires separate circuit breaker
Cold Water Run Option
MBTUH Amp
Draw
Model
Input Output
A
Width
K T
W
Heater Pump
Pump
Hp
Injector
Pump
Hp
Shipping
Weight
(Lbs.)
P 1532B
1530
1301
79-7/8 12
10
24-3/8
<12
12
3/4
1/3
1225
P 1802B
1800
1530
91-1/8 14
10
28-1/8
<12
12
3/4
1/3 *
1460
WHP 2002B
1999
1699
102-1/2 14
10
31-15/16
<12
14
1**
3/4 *
1560
WHP 2072B
2070
1760
102-1/2 14
10
31-15/16
<12
14
1**
3/4 *
1560
WHP 2342B
2340
1989
113-7/8 16
10
35-11/16
<12
21
1-1/2**
3/4 *
1620
Dimensions are in inches.
Ratings shown are for elevations up to 4,500 feet and for natural or propane gas.
For installation at elevations over 4,500 feet, please contact manufacturer.
Raypak, Inc. 2151 Eastman Avenue, Oxnard, CA 93030 (805) 278-5300 Fax (800) 872-9725 www.raypak.com
Max. Flow
Model
GPM
∆P (ft)
∆T
P 1532B
132
16.5
20
P 1802B
132
18.3
23
WHP 2002B
132
19.0
26
WHP 2072B
132
19.0
27
WHP 2342B
132
21.4
30