On vertical vents, the vent damper may be mounted with the actuator in any position. On horizontal vents,

do not mount the actuator either directly above or directly below the vent pipe; mount the vent damper actuator
to the side of the vent.

The vent damper is set up for a continuous pilot system. If the vent damper is installed on a system with an

Intermittent Pilot or Hot Surface Ignition the energy savings of the vent damper can be improved by plugging the hole
in the vent damper blade using the knockout plug, Part No. 105612R, provided in the parts envelope.

Hole in Vent Damper Blade

Closed Position

Fig. #8994

DO NOT plug the hole if installing the vent damper on a continuous pilot system as this will create a
hazardous condition.

Fig. #8183.0

INSTALLING THE VENT DAMPER IN HORIZONTAL
& VERTICAL VENT.

Fig. #152323

D80D GENERAL WIRING DIAGRAM

INSTALL THE VENT DAMPER TO SERVICE ONLY THE SINGLE APPLIANCE FOR WHICH IT IS INTENDED.
IF IMPROPERLY INSTALLED, A HAZARDOUS CONDITION, SUCH AS AN EXPLOSION OR CARBON
MONOXIDE POISONING, COULD RESULT.