Operating instructions Rinnai Q-Series

11

Water pressure in the central heating system

The installation will function optimally with a water

pressure of between 16 and 18 PSI.

If the water pressure drops below 12 PSI, the

display will show

FILL. During this message the

boiler will remain functioning at a reduced level.

After replenishing the system (see following

chapter) just above 22 PSI the message

FILL

will disappear and the boiler will function normally

again.

When the water pressure drops below 10 PSI, the

display will show a flashing

FILL text.

The boiler will shut down and will function normally

again after replenishing the system to just above

22 PSI.

To retreive the water pressure on the display from

the

Good reading:

- Press the Step key once briefly.

The water pressure will be shown.

Press the Step key briefly to return to the

Good

reading.

Water pressure is too high (>42 PSI), if HIGH

indication remains continuously visible, the boiler

is taken out of operation. The installation pressure

needs to be decreased by draining water until the

pressure is between 16 and 18 PSI.

Message ' Water pressure

too low' on your RS100

thermostat.

On the display of the RS100

a low water pressure can

be indicated. For further

information see the relevant

user manual.