87%-Efficiency Boilers –
Special Instructions

Water Piping

An 87%-efficiency boiler requires a minimum inlet
water temperature of 120ºF (49ºC) to prevent exces-
sive condensation in the combustion chamber. An
87%-efficiency boiler operated with an inlet tempera-
ture of less than 120ºF (49ºC) must have a manual
bypass or an approved low-temperature operation
system to prevent problems with condensation. A man-
ual bypass, shown in Fig. 15, must be piped into the
system at the time of installation. This piping is like a
primary/secondary boiler installation with a bypass in
the secondary boiler piping. Raypak strongly recomm-

NOTE: The constructions of the 84%- (standard)
and 87%-efficiency (optional) boilers are very similar,
and they are installed to the same requirements,
except as noted in this section.

ends that a thermometer be placed into the boiler inlet
piping next to the in/out header to facilitate tempera-
ture adjustment. Inlet water temperatures below 120ºF
(49ºC) can excessively cool the products of combus-
tion, resulting in condensation on the heat exchanger.

Venting

Appliance Categories

See Table P for appliance category requirements for
the 87%-efficiency Hi Delta.

CAUTION: Proper installation of flue venting is criti-
cal for the safe and efficient operation of the boiler.

NOTE: For additional information on appliance cat-
egorization, see appropriate code NFGC (U.S.) and
B149.1 (Canada), or applicable local building codes.

20°F T

30°F T

40°F T

Min. Flow

Max Flow

Model

No.

gpm

P (ft)

gpm

P (ft)

gpm

P (ft)

gpm

P (ft)

T

gpm

P (ft)

T

992AE

86

5.6

57

2.5

43

1.4

43

1.4

40

132

13.1

13

1262AE

110

10.3

73

4.6

55

2.6

55

2.6

40

132

14.8

17

1532AE

132

16.5

89

7.6

67

4.3

67

4.3

40

132

16.5

20

1802AE

N/A

N/A

104

11.5

78

6.5

78

6.5

40

132

18.3

24

2002AE

N/A

N/A

116

14.8

87

8.5

87

8.5

40

132

19.0

26

2072AE

N/A

N/A

120

15.8

90

9.1

90

9.1

40

132

19.0

27

2342AE

N/A

N/A

N/A

N/A

102

12.9

102

12.9

40

132

21.4

31

Note: Basis for minimum flow is 40°F T. Basis for maximum flow is 132 gpm.

Combustion

Air Supply

Exhaust

Configuration

Heater Venting

Category

Certified

Materials

Combustion Air

Inlet Material

Vertical Natural Draft

Venting

II

From Inside Building
(Non-Direct Venting)

Horizontal Through-

the-Wall Venting

IV

AL29-4C

Stainless Steel

(Gas Tight)

Vertical Natural Draft

Venting

II

From Outside Building

(Direct Venting)

Horizontal Through-

the-Wall Venting

IV

AL29-4C

Stainless Steel

(Gas Tight)

Galvanized Steel

PVC
ABS

CPVC

Table O: Heater Rate of Flow and Pressure Drop

Table P: Category Determination for Venting Purpose and Venting Arrangement

This manual is related to the following products: