beautypg.com

Can i use my humidifier with battery power – ResMed Compact Bilevel Device VPAP Auto User Manual

Page 3

background image

Consider a UPS in situations where the AC
power supply (standard mains electricity) is
intermittent or unreliable.

Table A: Types of Inverters

Converter

The VPAP Auto has a 24V DC power socket which
allows the connection of a 12V or 24V DC power
supply (ie, battery) using the ResMed
DC-12 Converter.

Converters are more efficient than inverters and
ResMed recommends that you use the DC-12
Converter if you are using a VPAP Auto
without a humidifier. The HumidAire 3i will not be
heated unless you use an inverter or UPS.

Battery

ResMed recommends using either a 12V or 24V
deep-cycle battery. The battery capacity that you
will require depends on your system’s power
consumption (see Table B). You will need a
charger for your battery.

Can I use my humidifier with battery
power?

Yes (Note: Only the HumidAire 3i integrated
heated humidifier is compatible with the VPAP
Auto). You will require a larger capacity battery

Setup

Output wave

Output Power Rating:
Continuous/Peak

VPAP Auto
(without
humidifier)

Modified or pure
sine wave

60W/225W

VPAP Auto
with
HumidAire 3i

TM

Pure sine wave:
110V
Pure sine wave:
240V

150W/500W

150W/500W

268159 VPAP Auto battery guide.qxp 7/12/2007 6:30 PM Page 6