SECTION L CONTROLS

WARNING:

Installation, adjustment and service of boiler controls including timing of various operating
functions must be performed by a qualified installer or service agency. Failure to do so may result in
control damage, boiler malfunction, property damage, personal injury, or death.

WARNING:

Turn off the power to the boiler before installation, adjustment or service of the Central Point Wiring
board or any boiler controls. Failure to do so may result in board damage, boiler malfunction,
property damage, personal injury, or death.

CAUTION:

This appliance has provisions to be connected to more than one (1) supply source. To reduce the risk
of electric shock, disconnect all such connections before servicing.

CAUTION:

Risk of electric shock. More than one (1) disconnect switch may be required to de-energize the
equipment before servicing.

CENTRAL POINT WIRING (CPW)

Central Point Wiring is an advanced control integration technique that provides complete boiler diagnostic capability
and greatly simplifies troubleshooting. At the heart of CPW is the Operations Status Center, which is comprised of two
different circuit boards: the CPW board and one or more U-2 Diagnostic Boards.

THE CPW BOARD

The Central Point Wiring (CPW) board serves as the central tie point for connecting all other control components in the
boiler. The CPW board provides boiler operating status and fault indication using eight LEDs which function as described
in Table L-1

Table L-1 CPW Board LED Indicators

Light

Color

Indication

Power

Green

24 VDC is applied to the system

System Error

Red

Overload current on the board. Board is disabled.

Pump

Green

Boiler Pump is energized.

Pilot

Yellow

Power applied to the Pilot Gas Valve. (PV signal on.)

Main Gas

Green

Power applied to Main Gas Valve. (MV signal on.)

Call for Heat

Green

Thermostat is closed. Call for heat present.

Service

Red (Flashing)

One or more of the safeties are open. Refer to U-2 Board

Blower

Green

Blower is energized.

This manual is related to the following products: