SECTION E: HYDRONIC HEATING PIPING

PUMP SELECTION

In order to insure proper performance of your boiler system, you must install a properly sized pump. Raypak recommends
using a 20°F

Delta

T as design

Delta

T. (

Delta

T is the temperature difference between the inlet and outlet water when the

boiler is firing at full rate). If a

Delta

T larger than 20°F is necessary, the bypass must be installed and adjusted to insure

proper hydraulics through the boiler while still allowing minimum flow to satisfy the safety flow switch. See Table D-1 for flow
rate requirements.