beautypg.com

4 vertical venting, 5 unvented operation tube termination, Figure 22: tube termination – Roberts Gorden Vantage twin Fire Unitary Infrared Heater TF-250 User Manual

Page 44: 6 length requirements, 7 horizontal ventilation 4" (10 cm) pipe

background image

TF-S

ERIES

I

NSTALLATION

, O

PERATION

AND

S

ERVICE

M

ANUAL

38

9.4 Vertical Venting

For 4" (10 cm), an approved vent cap
(P/N 90502300) must be used.
For 6" (15 cm) common vent, an approved vent cap
(P/N 90502302) must be used.
A vent shall not extend less than 2' (0.6m) above the
highest point where it passes through a flat roof of a
building.

9.5 Unvented Operation Tube Termination

Turndown type vent terminal with a screen must be
installed at the exhaust end of the tube. Vent terminal
design shall not incorporate backdraft flap.

FIGURE 22: Tube Termination

9.6 Length Requirements

The maximum vent length, where both tubes are
vented together is 45’ (13.7 m) of 6" (15 cm) diameter
duct. The maximum vent length, where both tubes
are vented individually is 45’ (13.7 m) of 4" (11 cm)
diameter duct, or 22.5’ (7 m) on each tube.

The maximum outside air supply duct length allowed
is 45’ (13.7 m) of either 4" (10 cm) or 5" (13 cm)
diameter, however the maximum length depends on
the venting arrangement used.

The total vent length, plus outside air duct length,
plus any extensions to minimum heat exchanger
lengths, cannot exceed 65' (19.8 m).

Vent length should be limited to less than 20' (6 m). If
using vent lengths greater than 20' (6 m),
condensation will form in the vent pipe. Insulation
and additional sealing measures (high temperature
silicone at all seams) are required. Optional heat
exchanger lengths are considered as vent length for
length determination.

Subtract 15' (4.6 m) of maximum allowed vent or duct
length per vent elbow if more than two are used.

9.7 Horizontal Ventilation 4" (10 cm) Pipe

Burner

Tube

Flexible

Boot

Vent Terminal

Combustible or

Non-Combustible

Wall

Single Wall

Vent Pipe

Metalbestos

Cap

4" (10 cm) Single Wall Pipe

Vent Terminal

18" (46 cm)

Min.

Non-Combustible

Wall

Approved

Wall

Thimble

Install with boot

extended

4" (10 cm) Single Wall Pipe

SIDE VIEW

Description

Part Number

Flexible Boot

91412800

Boot Clamp

91901300

Vent Terminal (Comb. Wall)

90502100

Vent Terminal

02537801-1P

Vent Sleeve

09080000