SECTION 8: OPTIONAL HEATER ACCESSORIES
8.1 U-Tube Configuration
The heaters are approved for optional U-Tube
configurations. This installation requires 1 or 2 U-
Tube packages depending on configuration desired.
Shown below is an example of a typical 80' (24 m) U-
Tube configuration. The U-Tube may be installed in
either a standard horizontal position or in an opposite
45° position as shown below. When designing a U-
Tube configuration, the following additional rules
must be adhered to:
• A minimum of 10' (3 m) on TF-120/160 and a min-
imum of 15' (4.5 m) on TF-200/250/300/ 350/380
is required between the burner and the U-Tube.
• The correct turbulator (
must be installed in the last standard section of
tube.
• The burner must never be operated in a tilted
position.
• When installed in a full 45° position, the burner
must be installed on the lower side.
• The heater must be properly supported at all loca-
tions.
WARNING
Cut/Pinch Hazard
Wear protective gear during installation,
operation and service.
Edges are sharp.
Failure to follow these instructions can result
in injury.