Figure 12: venting, 9, figure 12, Through – Roberts Gorden Vantage twin Fire Unitary Infrared Heater TF-250 User Manual
Page 15
SECTION 3: C
LEARANCES
TO
C
OMBUSTIBLES
9
NOTE: 1. All dimensions are from the surfaces of all tubes, couplings and elbows.
2. Clearances B, C and D can be reduced by 50% after 25' (7.5 m) of tubing downstream
from where the burner and burner tube connect.
FIGURE 12: VENTING
(inches)
(centimeters)
Model
A
E
F
A
E
F
TF-120
14
18
18
36
46
46
TF-160
20
24
18
51
61
46
TF-200
20
24
18
51
61
46
TF-250
20
24
18
51
61
46
TF-300
20
30
18
51
77
46
TF-350
20
30
18
51
77
46
TF-380
20
30
18
51
77
46
Radiant Tubes
Vent
Pipes
Unvented
Vented
A
E
F