Tremely easy to wire, Hydronic boiler hot water supply boiler - dhw, 120vac wiring center – Raypak XFYRE NINETY PLUS 500 User Manual

Page 6: Low voltage wiring center

background image

6

X

tremely Easy to Wire

300

28

17

19

8

14

5

14

5

40

36

27

17

500

47

16

31

7

24

4

24

4

40

56

24

18

850

80

40

53

17

40

10

40

10

40

80

40

20

XFyre

Model

20°F

GPM

⌬T

40°F

30°F

Minimum Flow*

Rates Of Flow And Pressure Drops

TYPE W

300

1693

1128

846

677

564

484

423

376

339

500

2821

1881

1411

1128

940

806

705

627

564

850

4796

3197

2398

1918

1599

1370

1199

1066

959

Temperature Rise (°F)

XFyre

Model

100

80

90

60

70

40

50

30

20

Recovery Rates

300

30

19

8

1.5

9

23

25

14

1.5

15

500

30

31

7

2

9

20

47

16

2

20

850

31

51

16

2

20

24

67

28

2

36

Soft

(0-4 Grains Per Gallon)

Water Hardness

Hard

(16-25 Grains Per Gallon)

Medium

(5-15 Grains Per Gallon)

XFyre

Model

Maximum Flow

GPM

⌬T

TYPE H

TYPE W

*Closed systems only

⌬P

⌬P

GPM

⌬P

GPM

⌬P

GPM

⌬P

⌬T

⌬P MTS

⌬T

GPM

SHL

GPM

MTS

⌬P

SHL

Do not use when hardness

exceeds 15 grains per gallon

MTS = Minimum Tube Size, inch.
SHL = System Head Loss, ft (based on heater and tank placed no more than 5 ft apart).
⌬T = Temperature rise,

°F

⌬P = Pressure drop through heat exchanger, ft

Hydronic Boiler

Hot Water Supply Boiler - DHW

⌬T GPM

MTS

⌬P

SHL

120VAC Wiring Center

The XFyre’s 120VAC wiring center is located on the rear
of the boiler. All incoming line voltage and pump wiring
are contained away from the 24v control wiring. Wiring
the boiler is simple and straight forward.

Low Voltage Wiring Center

Just like its big brother the XTherm, the XFyre has a
separate front mounted wiring center for all of the
low voltage connections. This makes thermostat, water
sensor, 0-10VDC BMS, and alarm contacts a breeze to
set up. No more guessing where the contact points
are buried in the boiler. Built-in cascade control using
CAT 3 or CAT 5 computer network patch cables to
connect with the communication bus between boilers.
Simply remove the front door for quick access.

120VAC Wiring Center

(rear of boiler)

Low Voltage

Wiring Center