Flue requirements - positioning – Rinnai HD70e User Manual
Page 8
8
Dime
J
L
H
H
K
F
I
nsion Terminal
Position
Distance
A
Directly below an opening, air brick, opening windows, etc.
300mm
B
Above an opening, air brick , opening window, etc.
300mm
C
Horizontally to an opening, air brick , opening window, etc.
300mm
D
Below gutters, soil pipes or drain pipes.
75mm
E Below
eaves.
200mm
F
Below balconies or car port roof.
200mm
G
From a vertical drain pipe or soil pipe.
150mm
H
From an internal or external corner.
200mm
I
Above ground, roof or balcony level.
300mm
J
From a surface facing the terminal.
600mm
K
From a terminal facing a terminal
1200mm
L
From an opening in a car port. ( e.g. door, window) into a dwell-
1200mm
M
Vertically from a terminal on the same wall.
1500mm
N
Horizontally from a terminal on the same wall.
300mm
O
From the wall on which the terminal is mounted
N/A
P
From a vertical structure on the roof.
N/A
Q
Above an intersection with roof.
N/A
FLUE REQUIREMENTS - POSITIONING