beautypg.com

Installation, Parts, General information – Regency U20 User Manual

Page 4: Clearances to combustibles

background image

4

U20/E21 Gas Insert Zero Clearance Kit

PARTS

Included with Kit:

1

Main Body Assembly (5 pieces)

1

Faceplate Top Insulation

1

Zero Clearance Top Louver Assembly

Sold Separately:

(Rq)=Required

(Rq)

1

402-918

Faceplate 40-1/4"W x 26-1/4"H
(1020mm W x 665mm H)
c/w faceplate trim.

(Rq)

1

532-926

4"(102mm) Hearth Trim

INSTALLATION

GENERAL INFORMATION

This kit consists of factory built parts that require minimal
assembly to form the Zero Clearance box for the U20/E21
Gas Insert. The Zero Clearance box can then be fixed into a
framed combustible construction, and a standard "B-vent"
installed on the assembly for the required venting. The
insert can be installed later. The faceplate will normally
overlap on top of the finished wall. Using Kit# 530-936 you
can convert the U20/E21 Gas Insert models into highly
efficient heat producing Zero Clearance Fireplaces.

CLEARANCES TO COMBUSTIBLES

The clearances for the Zero Clearance Kit are 0" to combustibles (back, side and floor) but when planning your
installation review the clearances required for the Insert (see below) after it is installed in the Zero Clearance Kit.

Clearances to Combustibles for Insert

The minimum clearance from the side of the appliance
to a combustible side wall is 9 inches (229mm). See the
"Mantel Clearances" chart (Diagram 2) for the minimum
clearance from the bottom of the Top Faceplate to a
combustible mantel. The minimum height from the
bottom of the Top Faceplate to the ceiling is 36 inches
(914mm). See diagram 1.

Diagram 2: Mantel can be installed anywhere in the
shaded area or higher. Use the grid to determine
height and depth of mantle.

Example: a 6" deep mantle must be 9" above the
bottom of the top faceplate.

Note:

A non-combustible mantel may be installed

at a lower height if the framing is made of metal studs
covered with a non-combustible board.

Note: Ensure the paint that is used on the mantel and the
facing is "heat resistant" or the paint may discolour.

Diagram 1

Diagram 2

The Zero Clearance Kit
must be installed on a
flat, solid, continuous
surface (e.g. wood,
metal, concrete). This
may be the floor, or
raised up on a platform
to enhance its visual
impact.

NOTE: The specified '0' inch floor clearance means that
the top surface of the flooring material, i.e. carpeting, tile,
etc., must not extend above the bottom edge of the 4"
Hearth Trim.

This manual is related to the following products: