Status LED
Status LED
Description
Status LED Troubleshooting Information
Yellow “ALERT”
Flash Code 3
Short Cycling
/ Compressor
is running only
briefl y
•
Thermostat demand signal is intermittent
•
Low line voltage (contact utility if voltage at disconnect is low)
•
Excessive liquid refrigerant in compressor
•
Compressor bearings are seized
Yellow “ALERT”
Flash Code 4
Locked Rotor
•
Run capacitor has failed
•
Low line voltage (contact utitlity if voltage at disconnect is
low)
•
Check wiring connections
•
Excessive liquid refrigerant in compressor
•
Compressor bearings are seized
•
Measure compressor oil level
Yellow “ALERT”
Flash Code 5
Open Circuit
•
Outdoor unit power disconnect is open
•
Compressor circuit breaker or fuse(s) is open
•
Compressor contactor has failed open
—
Check compressor contactor wiring and connectors
—
Check for compressor contactor failure (burned, pitted
or open)
—
Check wiring and connectors between supply and
compressor
— C
heck for low pilot voltage at compressor contactor coil
—
High pressure switch is open and requires manual reset
•
Open circuit in compressor supply wiring or connections
•
Unusually long compressor protector reset time due to extreme
ambient temperature
•
Compressor windings are damaged
—
Check compressor motor winding resistance
Yellow “ALERT”
Flash Code 6
Open Start Circuit
Current only in
run circuit
•
Run capacitor has failed
•
Open circuit in compressor start wiring or connections
—
Check wiring and connectors between supply and the
compressor S terminal
•
Compressor start winding is damaged
—
Check compressor motor winding resistance
Yellow “ALERT”
Flash Code 7
Open run circuit
Current only in
start circuit
•
Open circuit in compressor run wiring or connections
—
Check wiring and connectors between supply and the
compressor R terminal
•
Compressor run winding is damaged
—
Check compressor motor winding resistance
Yellow “ALERT”
Flash Code 8
Welded Contactor
Compressor
always runs
•
Compressor contactor has failed closed
•
Thermostat demand signal not connected to module
Yellow “ALERT”
Flash Code 9
Low Voltage
Control circuit
< 17VAC
•
Control circuit transformer is overloaded
•
Low line voltage (contact utility if voltage at disconnect is low)
•
Check wiring connections