Status LED

Status LED

Description

Status LED Troubleshooting Information

Yellow “ALERT”

Flash Code 3

Short Cycling
/ Compressor
is running only
briefl y

Thermostat demand signal is intermittent

Low line voltage (contact utility if voltage at disconnect is low)

Excessive liquid refrigerant in compressor

Compressor bearings are seized

Yellow “ALERT”

Flash Code 4

Locked Rotor

Run capacitor has failed

Low line voltage (contact utitlity if voltage at disconnect is
low)

Check wiring connections

Excessive liquid refrigerant in compressor

Compressor bearings are seized

Measure compressor oil level

Yellow “ALERT”

Flash Code 5

Open Circuit

Outdoor unit power disconnect is open

Compressor circuit breaker or fuse(s) is open

Compressor contactor has failed open

Check compressor contactor wiring and connectors

Check for compressor contactor failure (burned, pitted
or open)

Check wiring and connectors between supply and
compressor

C

heck for low pilot voltage at compressor contactor coil

High pressure switch is open and requires manual reset

Open circuit in compressor supply wiring or connections

Unusually long compressor protector reset time due to extreme
ambient temperature

Compressor windings are damaged

Check compressor motor winding resistance

Yellow “ALERT”

Flash Code 6

Open Start Circuit
Current only in
run circuit

Run capacitor has failed

Open circuit in compressor start wiring or connections

Check wiring and connectors between supply and the
compressor S terminal

Compressor start winding is damaged

Check compressor motor winding resistance

Yellow “ALERT”

Flash Code 7

Open run circuit
Current only in
start circuit

Open circuit in compressor run wiring or connections

Check wiring and connectors between supply and the
compressor R terminal

Compressor run winding is damaged

Check compressor motor winding resistance

Yellow “ALERT”

Flash Code 8

Welded Contactor
Compressor
always runs

Compressor contactor has failed closed

Thermostat demand signal not connected to module

Yellow “ALERT”

Flash Code 9

Low Voltage
Control circuit
< 17VAC

Control circuit transformer is overloaded

Low line voltage (contact utility if voltage at disconnect is low)

Check wiring connections

* Flash code number corresponds to a number of LED fl ashes, followed by a pause and then

repeated. Trip and alert LED’s fl ashing at same time means control circuit voltage is too low for
operation.

Table 4. LED Diagnostics - Continued

TROUBLESHOOTING - CONTINUED