Cooling Charging Charts

Figure 4. Charging Chart for 2 Ton Units

250

275

300

325

350

375

400

425

450

475

70

75

80

85

90

95

100 105 110 115 120 125

Liquid Temperature (° F)

Liquid Pressure (psig)

Remove refrigerant when above curve

Add refrigerant when below curve

Figure 5. Charging Chart for 3 Ton Units

Liquid Temperature (° F)

Liquid Pressure (psig)

250

275

300

325

350

375

400

425

450

475

500

70

75

80

85

90

95

100 105 110 115 120 125

Remove refrigerant when above curve

Add refrigerant when below curve