- 10 -
Maximum
production
The rated maximum steam production
for the humidifier
30802
Value written into Unit type
(40600) is also stored here
Alarms
The humidifier shall describe any faults
Too long to fill
Excess Current
End of cylinder life
No current
30364
Bit Allocation
Note More than one bit can be
active at any time.
Too long to fill = 1
Excess current = 2
End of cylinder life = 4
No Current = 8
Units
Required by the control board for
capacity calculations
40031
0: 0-1. 0=LBS, 1=KG
Unit type
Required by the control board for
current and capacity calculations
406000
Depending on the setting in
UNITS (Modbus: 40031)
Hex value representing
maximum unit capacity (100% fill
off amps)
Unit voltage
Required by the control board for
current and capacity calculations
40610
Format is Hexadecimal
numeration table (see below)
Hex
Value
Unit
Type
0
110-
120
1
208
2
220-
240
3
230
4
277
5
347
6
380
7
400
8
415
9
440-
480
A
550-
600
Unit phase
Required by the control board for
current and capacity calculations.
40620
Bit Allocation
Single phase = 1
Three phase = 2
Three phase (6 electrode) = 4