beautypg.com

Blower performance - fg7ta/tk – Nordyne iSEER FG7T User Manual

Page 4

background image

4

BLOWER PERFORMANCE - FG7TA/TK

FG7TA/TK - 80% AFUE, Two Stage Gas Furnace

Model Number

Heating

Input

(Btuh)

Motor Switch

Setting

External Static Pressure (in.w.c.)

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

1/5 2/6 3/7 4/8 CFM Rise CFM Rise CFM Rise CFM Rise CFM Rise CFM Rise CFM Rise CFM Rise

*TA/TK-060(C)-*A1 60000

0

0

0

0

1

0

0

0

0

1

0

0

600

74

555

80

510

1

1

0

0

705

63

670

66

635

70

600

74

0

0

1

0

775

57

740

60

705

63

665

67

1

0

1

0

900

49

870

51

835

53

800

56

765

58

730

61

695

64

660 67

0

1

1

0

950

47

920

48

890

50

855

52

825

54

795

56

765

58

730 61

1

1

1

0 1000

44

970

46

940

47

910

49

880

51

850

52

820

54

790 56

0

0

0

1 1075 41 1045

43

1015

44

985

45

960

46

925

48

900

49

870 51

1

0

0

1 1110 40 1080 41 1055 42 1025

43

1000

44

975

46

945

47

920 48

0

1

0

1 1170 38 1140 39 1115 40 1090 41 1060 42 1035

43

1010

44

985 45

1

1

0

1 1210

37

1185 38 1160 38 1130 39 1105 40 1080 41 1055 42 1025

43

0

0

1

1 1520 29 1225 36 1200

37

1175 38 1150 39 1120 40 1095 41 1070 42

1

0

1

1 1305

34

1280 35 1255 35 1230 36 1205

37

1180 38 1155 38 1130 39

0

1

1

1 1350

33

1230 36 1305

34

1285 35 1260 35 1240 36 1215

37

1195

37

1

1

1

1 1440 31 1400 32 1365

33

1230 36 1295 36 1255 35 1220 36 1185 38

*TA/TK-080(C)-*B1 80000

0

0

0

0

1

0

0

0

0

1

0

0

1

1

0

0

725

82

0

0

1

0

810

73

1

0

1

0

940

63

890

67

845

70

795

75

750

79

700

85

0

1

1

0

990

60

945

63

905

65

860

69

820

72

775

76

735

81

690 86

1

1

1

0 1055 56 1015 58

970

61

930

64

890

67

845

70

805

74

760 78

0

0

0

1 1135 52 1095 54 1055 56 1010 59

960

62

930

64

890

67

850 70

1

0

0

1 1185 50 1145 52 1105 54 1065 56 1030 58

990

60

950

62

910 65

0

1

0

1 1250

47

1210 49 1170 51 1135 52 1095 54 1055 56 1020 58

980 60

1

1

0

1 1290 46 1255

47

1220 49 1180 50 1145 52 1110 53 1075 55 1040 57

0

0

1

1 1315 45 1275 46 1240 48 1200 49 1160 51 1120 53 1085 55 1045 57

1

0

1

1 1350

44

1315 45 1280 46 1245 48 1205 49 1170 51 1135 52 1100 54

0

1

1

1 1390

43

1350

44

1315 45 1275 46 1240 48 1200 49 1160 51 1125 53

1

1

1

1 1420 42 1380

43

1345

44

1310 45 1270

47

1235 48 1200 49 1160 51

Notes:
1. Motor Switch Settings are for heating speeds using HEAT switches 1, 2, 3, & 4 and cooling speeds using COOL switches 5, 6, 7, & 8.
2. Two openings are recommended for airflows above 1600 CFM if the filter(s) is (are) adjacent to the furnace.
3. Data is shown without filter.
4. Temperature rises in the table are approximate. Actual temperature rises may vary.
5. Temperature rises that are shaded in grey are for reference only. These conditions are not recommended.