2 interrogating temperature calibration, Chapter 5: alarm programming 59 – Phonetics 1104 User Manual

Page 71

background image

Chapter 5: Alarm Programming

59

3.

Press the number (1 to 4) of the selected temperature
input to be calibrated.

4.

Enter the number required to offset the current tempera-
ture reading so a correct reading is obtained.

• To program a positive offset number (up to +10

degrees), enter the number on the keypad. The Model
1104 recites the digits as they are pressed.

• To program a negative offset number (up to –10

degrees), first press PAUSE. The unit responds with a
“beep.” Next, enter the number on the keypad. The unit
recites the digits as they are pressed.

5.

Press ENTER. The Model 1104 responds:“Enter.”

ENTER

TONE

PM

ENTER

TONE

PM

NOTE

If you find that your calibration offset exceeds
more than + 5 or – 5 degrees, other complicating
factors could be affecting normal operation of
the Model 1104. Call for technical
assistance.