Specifications
36
Powerware
®
9120 User's Guide
S
05147426 A Uncontrolled Copy
Table 8. Battery
Configuration
700 VA: (2) 12V, 7 Ah internal batteries; 24 Vdc
1000 VA: (3) 12V, 7 Ah internal batteries; 36 Vdc
1500 VA: (4) 12V, 7 Ah internal batteries; 48 Vdc
2000ć3000 VA: (8) 12V, 7 Ah internal batteries; 96 Vdc
EBM Configuration
PW9120 BAT-700: (4) 12V, 2 7 Ah; 24 Vdc
PW9120 BAT-1000: (6) 12V, 2 7 Ah; 36 Vdc
PW9120 BAT-1500: (8) 12V, 2 7 Ah; 48 Vdc
PW9120 BAT-3000: (16) 12V, 2 7 Ah; 96 Vdc
Type
Sealed, maintenanceĆfree, valveĆregulated, leadĆacid
Charging
Approximately 4 hours to 90% usable capacity at nominal line voltage after full load discharge
Table 9. Battery Run Times (in Minutes)
Number of Batteries
Run Times at Full/Half Load by UPS VA Ratings
Number of Batteries
700 VA
1000 VA
1500 VA
2000 VA
3000 VA
UPS Internal Batteries
7/18
7/18
7/18
12/34
6/15
1 EBM
34/70
36/80
29/67
49/107
30/70
2 EBMs
64/140
66/155
56/130
93/195
58/128
3 EBMs
141/310
87/191
4 EBMs
192/403
120/264
5 EBMs
240/504
148/325
NOTE
Battery times are approximate and vary depending on the load configuration and battery charge.