Communication port – Powerware 700 3000 VA User Manual
Page 32

Additional UPS Features
26
Powerware
®
9120 User's Guide
S
05147426 A Uncontrolled Copy
Communication Port
To establish communication between the UPS and a computer, connect
your computer to the UPS communication port using the supplied
communication cable.
When the communication cable is installed, power management
software can exchange data with the UPS. The software polls the UPS for
detailed information on the status of the power environment. If a power
emergency occurs, the software initiates the saving of all data and an
orderly shutdown of the equipment.
The cable pins are identified in Figure 12 and the pin functions are
described in Table 2.
3
8
7
9
1
6
2
4
5
Figure 12. Communication Port
Table 2. Communication Port Pin Assignment
Pin
Number
Signal Name Function
Direction from
the Multi-Port
Module
1
Low Batt
Low Battery relay contact
Out
2
RxD
Transmit to external device
Out
3
TxD
Receive from external device
In
RS-232 low
level signal for
>0.4 seconds
Conditional Power Off: In absence of AC
power, output is turned off until normal AC
power returns
In
4
Ċ
No Connection
Ċ
5
GND
Signal Ground
Ċ
6
Ċ
No Connection
Ċ
7
Ċ
No Connection
Ċ
8
AC Fail
AC Fail relay contact
Out
9
Power Source
+V (8 to 24 volts DC power)
Out