This UPS contains its own energy source (batteries). The output receptacles may
carry live voltage even when the UPS is not connected to an AC supply.
S
Do not remove or unplug the input cord when the UPS is turned on. This removes
the safety ground from the UPS and the equipment connected to the UPS.
S
To reduce the risk of fire or electric shock, install this UPS in a temperature and
humidity controlled, indoor environment, free of conductive contaminants. Ambient
temperature must not exceed 40
°
C (104
°
F). Do not operate near water or excessive
humidity (95% max).
S
To comply with international standards, the sum of earth leakage current from the
load connected to the UPS must not exceed 1 mA.
NOTE Do not make unauthorized changes to the UPS; otherwise, damage may occur
to your equipment and void your warranty.
Installing the Plug/Receptacle UPS
The following steps explain how to install the UPS. See UPS Rear
Panels" on page 6 for the rear panel of each model.
1. If you are installing power management software, connect your
computer to the UPS communication port using the supplied
communication cable.
2. If installing an optional Extended Battery Module, plug the
EBM cable into the battery connector on the EBM rear panel.
3. Plug the other end of the EBM cable into the battery connector
on the UPS rear panel.
4. If additional EBMs are to be installed, plug the EBM cable of the
second cabinet into the battery connector on the first EBM.
Repeat for each additional EBM.
5. On 208V or 230V models, plug the power cord into the input
connector on the UPS rear panel.
6. Plug the UPS power cord into a power outlet. The fan turns on
and the UPS enters Standby mode.