C H A P T E R 2

F

EATURES

This section covers:
S Using the communication port
S Starting the UPS on battery

Communication Port

Powerware Corporation offers an accessory interface kit that allows you

to connect many types of computer systems to the UPS communication

port. For specific information on Powerware Corporation interface kits,

call your service representative.

Pinouts

Contacts consist of open collector circuits capable of switching up to

+30 Vdc, 6 mA resistive load.

Table 1. Communication Port Pin Assignment

Pin

Signal Type

Function

1

RS-232 Level Shutdown

+12 Vdc signal held for 5 seconds on this pin shuts the UPS down

120 seconds later. The UPS restarts after 15 seconds when utility

power returns.

2

Not Used

Not Used

3

Normally Open On-Battery Contact

A normally open contact that closes 15 seconds (pulls to

Common) after the UPS switches to battery power.

4

Common

The signal ground for all signal pins.

5

Normally Open Low-Battery-Alarm Contact

A normally open contact that closes (pulls to Common) during a

Low Battery Alarm.

6

Normally Closed Low-Battery-Alarm Contact

A normally closed contact that opens (releases from Common)

during a Low Battery Alarm. This tells some shutdown software

when to start a computer shutdown.

7

Not Used

Not Used

8

Normally Closed On-Battery Contact

A normally closed contact that opens 15 seconds (releases from

Common) after the UPS switches to battery power.

9

Not Used

Not Used