Roubleshooting – Powerware 3110 User Manual
Page 17

13
Powerware
®
3110 User's Guide
S
05147486 B (English) Uncontrolled Copy
C H A P T E R 5
T
ROUBLESHOOTING
The front panel LEDs and an audible beep indicate the UPS status (see
Table 6). The UPS beeps whenever the unit is on battery power or an
alarm is present.
Table 6. Troubleshooting
Alarm or Condition
Possible Cause
What to Do
Normal operation.
None. The UPS is operating in Normal mode.
Line loss due to:
S Utility power outage.
S Wait for utility power to return.
S Loose plug connection.
S Check the power cord connections.
1 beep every 5 seconds
S Tripped circuit breaker.
S Reset the circuit breaker.
1 beep every 5 seconds.
S Power cord failure.
S Contact your service representative for a new power
cord.
2 beeps every 5 seconds.
Low battery alarm; shutdown is
imminent.
Prepare for a UPS shutdown. Save your work and turn
off your equipment.
The unit automatically restarts when acceptable power
returns.
3 beeps every 5 seconds.
The battery needs charging or
service.
Turn the UPS off and plug the UPS into a power outlet
for 24 hours to charge the battery. Turn the UPS on to
test the battery. If the alarm still beeps, see Replacing
Batteries" on page 7 to replace the battery.
3 beeps every 5 minutes.
The battery is discharged and
battery power is not available.
The UPS automatically recharges the battery. The alarm
clears when the battery is recharged.
NOTE
If the UPS has not recharged the battery after
24 hours, the alarm changes to 3 beeps every 5 seconds
and the battery must be replaced. See Replacing
Batteries" on page 7 to replace the battery.