Powerware 3110 User Manual
Page 16

Specifications
12
Powerware
®
3110 User's Guide
S
05147486 B (English) Uncontrolled Copy
Table 3. Battery
Configuration
250 VA: (1) 12V or (2) 6V, 4.2 Ah internal battery(s)
425 VA: (1) 12V, 7 Ah internal battery
600 VA: (1) 12V, 9 Ah internal battery
Voltage
12 Vdc
Type
Sealed, maintenanceĆfree, valveĆregulated, leadĆacid
Charging
8 hours to 95% capacity with output fully loaded
Monitoring
Advanced monitoring for earlier failure detection and warning
Backup Time
250ć425 VA: 3 minutes at full load; 5 minutes typical load
600 VA: 2.5 minutes at full load; 5 minutes typical load
Transfer Time
4 ms typical
Table 4. Weights and Dimensions
UPS Dimensions
(HxWxD)
250 VA: 5.9 x 39.3 x 15.0 cm (2.3I x 15.5I x 5.9I)
425ć600 VA: 7.9 x 37.6 x 17.2 cm (3.1I x 14.8I x 6.8I)
UPS Weight
250 VA: 3.0 kg (6.6 lb)
425 VA: 4.2 kg (9.2 lb)
600 VA: 4.3 kg (9.4 lb)
Table 5. Environmental and Safety
120V Model
230V Model
Operating Temperature
0°C to 40°C (32°F to 104°F)
Storage Temperature
-15°C to 50°C (-5°F to 122°F)
If the UPS is stored, the batteries should be recharged every 6 months.
If stored above 25°C (77°F), battery life is reduced and should be recharged more often.
Ventilation
Air around the unit must be free of dust, chemicals, or other materials
that corrode or contaminate.
Relative Humidity
5ć95% RH noncondensing
Audible Noise
(Normal mode)
Less than 40 dBA typical at one meter
Surge Energy Rating
450 joules
Surge Suppression
ANSI C62.41 Category A (formerly IEEE 587)
IEC 61000-4-5, Level 3
Safety Conformance
UL 1778; UL 497A;
CAN/CSA C22.2, No. 107.1
EN 50091-1-1 and IEC 60950
Safety Markings
UL, cUL
TUV/GS, CE
EMC (Class B)
FCC Part 15, ICES-003
EN 50091-2