Chapter 7: Programming

RECOGNITION

The recognition time is the length of time that an alarm condition must exist continuously
before ISACC will consider it a valid alarm and initiate a response. This keyword allows you
to program the recognition time for each input.

To display the currently programmed recognition times, type show recognition after an
ISACC prompt. You may also display the recognition time for a specific input by typing show
recognition

followed by the input number.

ISACC>show recognition

INPUT RECOGNITION TIME

IN01 = "LOW WELL FLOAT " = 000 Min 003 Sec

IN02 = "HI SUMP FLOAT " = 000 Min 003 Sec

IN03 = "Input #3 " = 000 Min 003 Sec

IN04 = "FLOW RATE (GPM) " = 000 Min 003 Sec

IN05 = "WELL LEVEL (FT) " = 000 Min 003 Sec

IN06 = "RESET " = 000 Min 003 Sec

IN07 = "Input #7 " = 000 Min 003 Sec

IN08 = "VOLTAGE " = 000 Min 003 Sec

IN09 = "Input #9 " = 000 Min 003 Sec

IN10 = "Input #10 " = 000 Min 003 Sec

IN11 = "Input #11 " = 000 Min 003 Sec

IN12 = "Input #12 " = 000 Min 003 Sec

IN13 = "Input #13 " = 000 Min 003 Sec

IN14 = "Input #14 " = 000 Min 003 Sec

IN15 = "Input #15 " = 000 Min 003 Sec

IN16 = "Input #16 " = 000 Min 003 Sec

To program the recognition times, type set recognition after an ISACC prompt. Enter a new
value for the minutes and press ENTER. Enter a new value for the seconds and press EN-
TER to go to the next parameter. You may also program the recognition time of a specific
input by typing set recognition followed by the input number.

ISACC>set recognition

INPUT RECOGNITION TIME

IN01 = "LOW WELL FLOAT " = 000 Min 003 Sec

New minutes >

New seconds >001

IN02 = "HI SUMP FLOAT " = 000 Min 003 Sec

New minutes >

New seconds >001

IN03 = "Input #3 " = 000 Min 003 Sec

New minutes >

New seconds >001

IN04 = "FLOW RATE (GPM) " = 000 Min 003 Sec

New minutes >001 New seconds >030

IN05 = "WELL LEVEL (FT) " = 000 Min 003 Sec

New minutes >005 New seconds >000

IN06 = "RESET " = 000 Min 003 Sec

New minutes >

New seconds >

IN07 = "Input #7 " = 000 Min 003 Sec

New minutes >010 New seconds >000

IN08 = "VOLTAGE " = 000 Min 003 Sec

New minutes >001 New seconds >030

IN09 = "Input #9 " = 000 Min 003 Sec

New minutes >

New seconds >

IN10 = "Input #10 " = 000 Min 003 Sec

New minutes >

New seconds >

IN11 = "Input #11 " = 000 Min 003 Sec

New minutes >

New seconds >

IN12 = "Input #12 " = 000 Min 003 Sec

New minutes >

New seconds >

IN13 = "Input #13 " = 000 Min 003 Sec

New minutes >

New seconds >

IN14 = "Input #14 " = 000 Min 003 Sec

New minutes >

New seconds >

IN15 = "Input #15 " = 000 Min 003 Sec

New minutes >

New seconds >

IN16 = "Input #16 " = 000 Min 003 Sec

New minutes >

New seconds >