remove the acrylic panel. Using needlenose pliers, move the shunt to the appropriate position.
See diagrams below. Replace the acrylic panel when finished.

TEMP position

- The default configuration connects the input signal to a 5V reference

through a 6.34K pull-up resistor. This configuration allows a thermistor, dry contact (N.C. or
N.O. ), or pulse counting sensor to be wired to the input. You may use either a 2.8K ther-
mistor or a 10K thermistor with ISACC.

P12

TEMP

4-20mA

1

Thermistor, dry contact or pulse count configuration

4-20mA position

- This configuration connects the input signal to a 249 Ohm load resistor.

This allows ISACC to measure the current at the input. Any sensor that puts out 4-20mA can
be wired to this input.

P12

TEMP

4-20mA

1

4-20mA configuration

0-5V (NO SHUNT) position

- This configuration connects the input signal directly to

ISACC’s analog to digital converter for measuring the output of 0 to 5 volt transducers. Any
sensor that puts out 0-5V can be wired to this input.

P12

TEMP

4-20mA

1

0-5 Volt configuration

CAUTION: Wiring sensors with shunts in the incorrect position could result in
damage to the unit.