Troubleshooting – Lochinvar KNIGHT 81-286 User Manual

Page 43

background image

3

Troubleshooting

Service Manual

43

Table 3-4 (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Boiler Interface

FAULT

DESCRIPTION

CORRECTIVE ACTION

Low 24 vac

120 vac input to the main control board has
dropped below 80 vac.

• Check 120 vac supply to the transformer.

• Check wiring connections at the low voltage

terminal strip.

• Check the wire size/length to remote devices.

• Replace the transformer.

Watch Dog Error

The main control board has detected an
internal fault.

• Replace the main control board.

Write EEProm

The main control board has detected an
internal fault.

• Replace the main control board.

CRC Parameters

The main control board has detected an
internal fault.

• Replace the main control board.

No Error Stored

The main control board has detected an
internal fault.

• Replace the main control board.