System and Control Options
42
7.8
Setup Operation
The AC4’s operation features allow you to set up a rotation sequence to
alternate which devices are operating and which are placed on
Standby, as well as test devices while in Standby mode and specify
what to do when a Standby device goes into alarm as it is powered up.
You may also specify delay times after an output changes state, direct-
ing the AC4 to wait before acknowledging inputs or turning an output
on or off.
To change any operation features:
Log In and Choose Setup System
• From the Main Menu, use the arrows
↑↓
to
choose System and
Control, then press Enter
↵
(see 7.1 - Login for help)
.
• Enter your password at the Login screen.
• From the System and Control Menu, use the arrows
↑↓
to
choose
Setup System, then press Enter
↵
.
Select Setup Operation
• From the Setup System Menu, shown at right, use the arrows
↑↓
to
choose Setup Operation and press Enter
↵
.
• Use the steps following Table 18 to access any of the Setup Operation options.
Table 18 shows the default settings for operation options: automatic sequencing, standby testing,
failed standby, hold delay and restart.
Table 18
Default settings - operation features
Feature
Default
Other Options
AUTO SEQUENCING
OFF (Deactivated)
ON (Activated), 12h (Activated for 12-hour intervals)
STANDBY TESTING
OFF (Deactivated)
ON (Activated)
FAILED STANDBY
N (Deactivated)
Y (Activated)
HOLD DELAY
10:00 (No delay)
Any time (in minutes and seconds) from 00:00 to 99:59
RESTART
00:06 (No delay)
Any time (in minutes and seconds) from 00:00 to 99:59
Setup System Menu
SETUP INPUTS
SETUP COMMON ALARM
SETUP ZONES
↑↓
=NEXT
↵
=SELECT
SETUP OUTPUTS
SETUP SYSTEM INFO
> SETUP OPERATION
Setup Operation Menu
> AUTO SEQUENCING OFF
STANDBY TESTING OFF
FAILED STANDBY
N
↑↓
=NEXT
↵
=SELECT
HOLD DELAY : 10:00
RESTART
: 00:06