0 wiring and connections, 1 wiring specifications, Table 4 wiring specifications – Liebert AC4 User Manual
Page 18: Iring, Onnections, Wiring specifications, Table 4, Wiring and connections, Caution
Wiring and Connections
12
3.0
W
IRING
AND
C
ONNECTIONS
3.1
Wiring Specifications
Input and output connections to the AC4 may be made in any order—it is not necessary, for example,
to make all input connections before making any output connections. Use copper conductors only for
all wiring.
!
CAUTION
Switch OFF electric power to the AC4 before installing any wiring to the unit or changing
input or output connections. The Power On/Off switch is in the top left corner of the unit.
Table 4
Wiring specifications
Connection
Supported Wire Type
Maximum Wire Length
Rating
Digital
Input
18-22 AWG Stranded & Unshielded
18 AWG* (recommended)
Non Plenum - Belden 9740
Plenum - Belden 89740
750 ft. (225m)
Dry Contact
(24VDC, 10 mA)
Digital
Output
18-22 AWG Stranded & Unshielded
18 AWG* (recommended)
Non Plenum - Belden 9740
Plenum - Belden 89740
18 AWG*
(recommended)
20 AWG
22 AWG
24VAC @3A
@3A 50 ft. (15m)
@2A 100 ft. (30m)
@1A 200 ft. (60m)
@3A 40 ft. (12m)
@2A 60 ft. (18m)
@1A 100 ft. (30m)
@3A 25 ft. (7m)
@2A 35 ft. (10m)
@1A 75 ft. (23m)
Common
Alarm
Output
18-22 AWG Stranded & Unshielded
18 AWG* (recommended)
Non Plenum - Belden 9740
Plenum - Belden 89740
18 AWG*
(recommended)
20 AWG
22 AWG
24VAC @3A
@3A 50 ft. (15m)
@2A 100 ft. (30m)
@1A 200 ft. (60m)
@3A 40 ft. (12m)
@2A 60 ft. (18m)
@1A 100 ft. (30m)
@3A 25 ft. (7m)
@2A 35 ft. (10m)
@1A 75 ft. (23m)
Communication
RS232
Null Modem Cable
50 ft. (15m)
N/A
24VAC Power
Connection
(TB7)
18-22 AWG Stranded & Shielded
18 AWG* (recommended)
Non Plenum - Belden 8770
Plenum - Belden 88770
150 ft. (45m)
24VAC @1.3A
* Recommended