beautypg.com

LG 395CAV User Manual

Page 6

background image

4. Adjust outside nut to provide desired height, and tighten

inside nut to secure arrangement.

V.

GAS PIPING

Gas piping must be installed in accordance with national and local
codes. Refer to the current edition of the NFGC. Canadian
installations must be installed in accordance with NSCNGPIC and
all authorities having jurisdiction.

Refer to Table 4 for the recommended gas pipe size. Risers must
be used to connect to the furnace and the meter.

CAUTION:

If a flexible connector is required or al-

lowed by the authority having jurisdiction, black iron
pipe shall be installed at the gas valve and extend a
minimum of 2 in. outside the furnace casing.

Piping should be pressure tested in accordance with local and
national plumbing and gas codes before the furnace has been
attached. If the pressure exceeds 0.5 psig (14-in. wc), the gas
supply pipe must be disconnected from the furnace and capped
before the pressure test. If the test pressure is equal to or less than
0.5 psig (14-in. wc), turn off electric shutoff switch located on the
gas valve before the test. It is recommended that the ground joint
union be loosened before pressure testing. After all connections
have been made, purge the lines and check for leakage with
regulated gas supply pressure.
Install a sediment trap in the riser leading to the furnace. The trap
can be installed by connecting a tee to the riser leading from the
furnace. Connect a capped nipple into the lower end of the tee. The
capped nipple should extend below the level of the gas controls.
(See Fig. 7.)
Apply joint compound (pipe dope) sparingly and only to the male
threads of each joint. The compound must be resistant to the action
of propane gas.
An accessible manual shutoff valve MUST be installed upstream
of the furnace gas controls and within 72 in. of the furnace. A
1/8-in. NPT plugged tapping, accessible for test gage connection,
MUST be installed immediately upstream of the gas supply
connection to the furnace and downstream of the manual shutoff
valve. Place ground joint union between the gas control manifold
and the manual shutoff valve.

Fig. 5—Bottom Filter Arrangement

(Control Removed for Clarity)

A96030

WASHABLE
FILTER

FILTER
SUPPORT

FILTER
RETAINER

24

1

2

-IN. WIDE

CASINGS ONLY:
CUT AND FOLD
FACTORY-PROVIDED
FILTERS AS SHOWN
TO DESIRED SIZE.

17

1

2

-IN. WIDE

CASINGS ONLY:
INSTALL FIELD-SUPPLIED
FILTER FILLER STRIP
UNDER FILTER.

1

24

1

/

2

3

TABLE 3—FILTER INFORMATION (IN.)

FURNACE

CASING WIDTH

FILTER SIZE*

FILTER TYPE

Side Return

Bottom Return

14-3/16

(1) 16 X 25 X 1†

(1) 14 X 25 X 1

Cleanable

17-1/2

(1) 16 X 25 X 1†

(1) 16 X 25 X 1

Cleanable

21

(1) 16 X 25 X 1

(1) 20 X 25 X 1†

Cleanable

24-1/2

(2) 16 X 25 X 1†

(1) 24 X 25 X 1

Cleanable

* Filters can be field modified by cutting the frame as marked and folding to the
desired size. Alternate sizes can be ordered from your distributor or dealer.
† Factory-provided with the furnace.

Fig. 6—Leveling Leg Installation

A89014

1

3

4

1

3

4

1

3

4

1

3

4

5

16

5

16

5

16

5

16

TABLE 4—MAXIMUM CAPACITY OF PIPE*

NOMINAL IRON

PIPE SIZE

(IN.)

INTERNAL

DIAMETER

(IN.)

LENGTH OF PIPE (FT)

10

20

30

40

50

1/2

0.622

175

120

97

82

73

3/4

0.824

360

250

200

170

151

1

1.049

680

465

375

320

285

1-1/4

1.380

1400

950

770

660

580

1-1/2

1.610

2100

1460

1180

990

900

* Cubic ft of gas per hr for gas pressures of 0.5 psig (14-in. wc) or less, and a
pressure drop of 0.5-in. wc (based on a 0.60 specific gravity gas). Ref: Table
10-2 NFPA 54-1992.

—6—