beautypg.com

Maintenance schedule, Service technician, Owner maintenance – Lochinvar KNIGHT XL 400 User Manual

Page 5

background image

2

Maintenance schedule

5

ƽ WARNING Follow the maintenance procedures given throughout this manual. Failure to perform the service and

maintenance or follow the directions in this manual could result in damage to the boiler or system,
resulting in severe personal injury, death, or substantial property damage.

User’s Information Manual

Service technician

(see the Knight XL Service Manual)

General:

Address reported problems

Inspect interior; clean and vacuum
if necessary

Clean condensate trap and fi ll with
fresh water

Check for leaks (water, gas, fl ue,
condensate)

• Verify

fl ue and air lines in good

condition and sealed tight

Check system water pressure/
system piping/expansion tank

Check control settings

Check ignition and fl ame sense
electrodes (sand off any deposits;
clean and reposition)

Check wiring and connections

Perform start-up, checkout and
performance verifi cation per Sec-
tion 10 in the Knight XL Installation
and
Operation manual

Flame inspection (stable, uniform)

Flame signal (at least 10
microamps at high fi re)

Clean the heat exchanger if fl ue
temperature is more than 54°F
(30°C) above return water
temperature

If combustion or performance
indicate need:

Clean heat exchanger

Remove and clean burner using
compressed air only

Clean the blower wheel

Owner maintenance

(see pages 6 - 8 for detailed instructions)

Daily

Check boiler area

• Check

pressure/

temperature gauge

Monthly

Check vent pipng

Check air piping

Check air and vent a

• termination

screens

Check relief valve

Check condensate drain
system

Check air vents

Periodically

Test low water cutoff
(if used)

Reset button (LWCO)

Every

6 months

Check boiler piping
(gas and water) for leaks

Operate relief valve

End

of season

months

Shut boiler down
(unless boiler is used for
domestic hot water)

ANNUAL START-UP