Service Manual 69

Troubleshooting Guide

Turn on the main power.

When in air circulation mode, compressor/outdoor fan is stopped.

Turn off main power.

Check the electrical wiring diagram of Outdoor side.
Check the open or short of connecting wires between Indoor and Outdoor.

Check the sensor for Indoor temperature is attatched as close as to be effected by the
themperature of Heat Exchange (EVA.)

When the sensor circuit for Indoor temperature and connector are in bad connection or are
not engaged, Compressor/Outdoor fan is stopped.

• Check the related circuit of R01H(1K), R02H(1K), R03H(1K), R04H(1K), Micom(pin No.

74 ,

75 , 76 , 77

).

• Check the Indoor temperature sensor is disconnected or not (about 10K at 25°C).

Check the Relay(RY-PWR, RY-START) for driving Compressor.

• Check the voltage between brown and blue cable of terminal to connect the Outdoor

(About AC208V / 230V).

• Check the related circuit of relay in Outdoor PCB Ass'y.

Operate Cooling Mode by setting the disired temperature of the remote controller is less
than one of the Indoor temperature by 1°C at least.

The Compressor/Outdoor Fan are don't operate

Trouble 3

Check Point

Between Micom(No. 50,51) and
GND

DC 5V

DC 0V

DC 12V

DC 1V

Between IC01M(No. 10) and
GND

Comp. ON

Comp. OFF