G24−200 FIELD WIRING DIAGRAM (120V SINGLE PH 60HZ)

PRIMARY

LIMIT

PRESSURE

SWITCH

G

Y1

IGNITION

CONTROL

BOARD

L1

N

FUSED OR CIRCUIT BREAKER

DISCONNECT

(Furnished by

installer)

THERMOSTAT

C

GND

GAS

VALVE

W1

DOOR

INTERLOCK

PRIMARY

LIMIT

PRESSURE

SWITCH

DOOR

INTERLOCK

GAS

VALVE

FLAME ROLLOUT

SWITCH

K3 CONTACTOR

T3 TRANSFORMER

See Note 3

T1 TRANSFORMER

24v: blue − yellow

120v: black − white

R

W2

Y2

G

Y1

C

W1

R

W2

Y2

ECONOMIZER

RELAY

TB34

4

L1

ECON

L2 L3

T3

T2

T1

L1

L3

3

1 2

4

K13

J84

T13 TRANSFORMER

See Note 3

7

K105

BLUE

YELLOW

BLACK

7

5

RELAY

K109

BLOWER MOTOR

CONTROL BOX

RELAY

TB1 TERMINAL STRIP

TERMINAL STRIP

MAKE−UP BOX

L1

L3

PLUG

BLOWER DECK

BLUE

YELLOW

RED

RED

BLUE

BLACK

RED

RED

RED

RED

(Alternate make-up
box left side)

(Alternate make-up
box right side)

See Note 1

NOTES :

1 − Relay K109 can be used for an accessory rated at the same voltage as power supply.

REMOVE FACTORY-
INSTALLED JUMPER IN
TWO-STAGE MODE

WHITE

BLUE

2 − Field installed and supplied resistor (R3), is required in two-stage applications when using electro-mechanical thermo-
stat. (Use a 150 ohm, 10 watt resistor − Lennox part number P−8−6256.)

R3

See Note 2

COMBUSTION

AIR BLOWER

COMBUSTION

AIR BLOWER

IGNITION

CONTROL

BOARD

GROUND
LUG

MAKE-UP BOX

RED

WHI

T

E

RED

BLACK

WHI

T

E

FACTORY INSTALLED

LINE VOLTAGE FIELD INSTALLED
24 VOLTS FIELD INSTALLED

FIELD-INSTALLED DRIVE KIT COMPONENT

3 − The T3 and T13 transformers (54G5201) are marked as follows: 230v between white and black leads and 460v between
white and red leads. However, in this application, each transformer has been used to supply 230v (available between the
white and red leads) to an induce draft blower when 115v is applied between the white and black leads of each transformer.

FIGURE 15