A
Building Safety. Building Security.
Specifi cations
Current consumption at 24V (without detectors/modules)
typ. 25mA
Number of detector zones
max. 144
Number of detectors/modules
System Sensor/200 protocol
max. 318 elements (159 detectors + 159 modules)
Apollo/Discovery protocol
max. 126 elements
Labor Strauss/700 protocol
max. 240 elements
Idle loop current
typ. 300µA per detector/module
Total loop current
max. 500mA (at reduced line resistance)
Idle loop voltage
System Sensor/200 protocol
typ. 29V
Apollo/Discovery protocol
typ. 26V
Labor Strauss/700 protocol
typ. 29V
Loop line resistance
max. 50Ω per core
Ambient temperature
-5°C to +50°C
Dimensions L × W × H
132 Ч 74 Ч 23 (mm)
Weight
80g
Order number
214037
Order name
Loop Interface LIF128-1
Usually, the loop wiring is realised as ring. Thanks to the
ring-shaped wiring, all elements on the loop keep wor-
king in the event of a single wire breakage. If necessary,
branch lines can also be connected to the ring.
In the event of a short circuit, the functioning of the loop
elements that are cut off from the faulty loop segment
by means of isolators, can be maintained. The control
panel indicates a wire breakage or a short circuit as
loop fault.
Unshielded wires can be used for the fi re detector ca-
bling and, therefore, existing installations can be adop-
ted very easily and existing cabling can be reused.