User’s Information Manual

2

Maintenance schedule

5

Service technician

General:

• Address reported problems

• Inspect interior; clean and vacuum if

necessary;

• Check for leaks (water, gas, flue,

condensate)

• Examine venting system

• Check system water pressure/system

piping/expansion

tank

• Check control settings

• Check igniter

• Check wiring and connections

• Check flue gas passageways

• Flame inspection (stable, uniform)

Inspect and clean the burner


• Check manifold gas pressure

Perform start-up checkout and

performance verification per Section 6

in the Copper-fin II Installation and Operation

Manual

If combustion or performance

indicate need:

• Clean heat exchanger with a stiff bristle

brush


Remove and clean burners using

water. Dry before re-assembling.

• Clean the blower wheel with a brush and

vacuum. Do not let dirt from cleaning get
pulled into the blower.

Owner maintenance

(see pages 6 - 7 for detailed instructions)

Daily

• Check boiler area

Check pressure/temperature

gauge

Monthly

• Check vent piping

• Check air piping

• Check relief valve

• Replace combustion air filter

Note: More frequent replacement
may be necessary in dirty
environments.

Periodically

• Test low water cutoff (if used)

• Reset button (low water cutoff)

Every

6 months

• Check boiler piping (gas and

water) for leaks

• Operate relief valve

End

of season

months



• Shut boiler down (unless boiler

used for domestic hot water)

ƽ WARNING

Follow the maintenance procedures given throughout this manual. Failure to perform the service and
maintenance or follow the directions in this manual could result in damage to the boiler or system,
resulting in severe personal injury, death, or substantial property damage.

ANNUAL START-UP