Smart system control module – Lochinvar COPPER-FIN II 402 - 2072 User Manual

Page 15

background image

15

4

SMART SYSTEM control module

(continued)

Status Display Screens

(cont’d)

By using the Previous/Next (, ) arrow keys on the SMART SYSTEM display panel, you can navigate through the 11 display
screens. Each screen will contain two (2) viewable items. The following is a description of the individual items and what they
can display:

Screen

Display shows:

Description

Press the Next  arrow key on the SMART SYSTEM display to access Screen #5.

Screen #5

Line 1

0 – 10V BMS: **.*V

The control displays the BMS voltage input from 0 to 10 volts.

Screen #5

Line 2

STG DEMAND: ****

The control displays the number of stages being called by the control.

Press the Next  arrow key on the SMART SYSTEM display to access Screen #6.

Screen #6

Line 1

FAN SPEED: ***

The control will display either OFF, LOW, or HIGH depending upon
fan speed requirements of number of stages firing.

Screen #6

Line 2

0 – 10V RATE: **.*V

The control will display 0 to 10 volts based upon the number of stages
firing.

Press the Next  arrow key on the SMART SYSTEM display to access Screen #7.

Screen #7

Line 1

SH CFH: ***

The control will display either ON or OFF based upon a demand (call
for heat) for space heating.

Screen #7

Line 2

WHR CFH: ***

The control will display either ON or OFF based upon a demand (call
for heat) for DHW (domestic hot water).

Press the Next  arrow key on the SMART SYSTEM display to access Screen #8.

Screen #8

Line 1

SYS PUMP: ***

The control will display either ON or OFF based upon system pump
requirements upon demand for space heating.

Screen #8

Line 2

SYSPUMPSPD: **.*V

The control will display the 0 – 10V input voltage from the system
pump based upon system pump speed.

Press the Next  arrow key on the SMART SYSTEM display to access Screen #9.

Screen #9

Line 1

UNIT PUMP: ***

The control will display either ON or OFF based upon unit pump
requirements upon demand for space heating.

UNIT PUMP: DELAY

The control will display delay in unit pump operation after the space
heating requirements have been satisfied.

Screen #9

Line 2

DHW PUMP: ***

The control will display either ON or OFF based upon unit pump
requirements upon demand for DHW.

DHW PUMP: DELAY

The control will display delay in unit pump operation after the DHW
requirements have been satisfied.

Press the Next  arrow key on the SMART SYSTEM display to access Screen #10.

Screen #10

Line 1

FLM SIG – A: **.* µA

The control displays the igniter flame signal of igniter A in microamps.

Screen #10

Line 2

FLM SIG – B: **.* µA

The control displays the igniter flame signal of igniter B in microamps.

Press the Next  arrow key on the SMART SYSTEM display to access Screen #11.

Screen #11

Line 1

IGN * AMPS: *.* A

The control displays the current of either igniter A or B.

Screen #11

Line 2

MIX VAL POS: ** %

The control displays the mixing valve percentage open to the system.

User’s Information Manual