Wwarning, 22 connecting electric dryers – LG PROTOCOL P154 User Manual
Page 22
22
CONNECTING ELECTRIC DRYERS
(cont.)
Remove 3
1
⁄
2
inches (8.9 cm) of the outer
covering from the wire. Strip 1 inch (2.5 cm)
insulation from each wire. Bend the ends of
the three wires into a hook shape.
1
Attach the two hot leads of the power cord
to the outer terminal block screws. Attach
the neutral wire to the center terminal block
screw. Connect the external ground (if
required by local codes) to the green ground
screw. TIGhTEN ALL SCREWS SECURELY.
Reinstall the terminal block access cover.
3
Ground Screw
Neutral
(White)
hot
Black)
Ground Wire
hot
(Red)
Remove the terminal block access cover
on the upper back of the dryer. Install a
UL-listed strain relief into the power cord
through-hole; then thread the power cable
prepared in Step 1 through the strain relief.
2
UL-Listed
Strain Relief
UL-Listed
3-Wire
Power Cord
Terminal
Block
1" (2.5 cm)
Three-Wire Connection for Electric Dryers: Direct Wire
• A 3-wire connection is NOT permitted on new
construction after January 1, 1996.
• A UL-listed strain relief is required.
• Use UL-listed
3-wire #10 AWG-minimum
copper conductor cable.
• Allow at least 5 ft (1.5 m) length to allow for
removal and reinstallation of the dryer.
w
WARNING:
• Connect the power cord to the terminal block. Each colored wire should be connected
to same color screw. Wire color indicated on manual is connected to the same color
screw in block. Failure to follow these instructions may result in a short or overload.
• Grounding through the neutral conductor is prohibited for: (1) new branch-circuit
installations, (2) mobile homes, (3) recreational vehicles, and (4) areas where local
codes prohibit grounding through the neutral conductor.
USA ONLY